Citas bibligráficas
Esta es una referencia generada automáticamente. Modifíquela de ser necesario
Göpfert, J., (2021). Model-based fault diagnosis via structural analysis of a reverse osmosis plant [Pontificia Universidad Católica del Perú]. http://hdl.handle.net/20.500.12404/19043
Göpfert, J., Model-based fault diagnosis via structural analysis of a reverse osmosis plant []. PE: Pontificia Universidad Católica del Perú; 2021. http://hdl.handle.net/20.500.12404/19043
@mastersthesis{renati/536233,
title = "Model-based fault diagnosis via structural analysis of a reverse osmosis plant",
author = "Göpfert, Johannes Georg",
publisher = "Pontificia Universidad Católica del Perú",
year = "2021"
}
Título: Model-based fault diagnosis via structural analysis of a reverse osmosis plant
Autor(es): Göpfert, Johannes Georg
Asesor(es): Pérez Zúñiga, Carlos Gustavo; Reger, Johann
Palabras clave: Agua--Tratamiento--Ósmosis inversa; Modelos matemáticos; Fallas estructurales
Campo OCDE: http://purl.org/pe-repo/ocde/ford#2.02.03
Fecha de publicación: 11-may-2021
Institución: Pontificia Universidad Católica del Perú
Resumen: Water desalination is one approach to force water scarcity. One of the processes used for
desalination is reverse osmosis. Like other systems, a reverse osmosis plant is susceptible to
faults. A fault can lead to a loss of efficiency, or if the fault is severe to a total breakdown.
Appropriate measures can minimize the impact of faults, but this requires in time fault
detection.
The following thesis shows a proposal for an online fault diagnosis system of a reverse
osmosis plant. For the model-based approach, a mathematical model of a reverse osmosis
plant has been developed. The model contains a new approach for modeling the interaction
between the high-pressure pump, the brine valve, and the membrane module. Furthermore,
six faults considered for fault diagnosis have been modeled. Two of the faults are plant
faults: The leakage of the feed stream and membrane fouling. The other four faults are
sensor or actuator malfunctions.
The fault diagnosis system is developed via structural analysis, a graph-based approach to
determine a mathematical model’s overdetermined systems of equations.
With the structural analysis, 73 fault-driven minimal structurally overdetermined (FMSO)
sets have been determined. The results show that all six faults are detectable. However, two
faults are not isolable. Five of the FMSO sets have been chosen to deduce the residuals used
for online fault detection and isolation. The simulations demonstrate that the calculated
residuals are appropriate to detect and isolate the faults. If one assumes that only the
considered faults occur, it is possible to determine some faults’ magnitude.
Enlace al repositorio: http://hdl.handle.net/20.500.12404/19043
Disciplina académico-profesional: Ingeniería de Control y Automatización
Institución que otorga el grado o título: Pontificia Universidad Católica del Perú. Escuela de Posgrado.
Grado o título: Maestro en Ingeniería de Control y Automatización
Jurado: Reger, Johann; Pérez Zúñiga, Carlos Gustavo; Sotomayor Moriano, Juan Javier
Fecha de registro: 11-may-2021
Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons