Cevallos, C., Ninancuro, M. (2021). Evaluación del comportamiento Físico-mecánico de las unidades de ladrillo de concreto para albañilería, elaboradas con árido de residuos de construcción y demolición (R.C.D.) y cemento Pórtland tipo IP, fabricadas en la ciudad de Cusco [Universidad Andina del Cusco]. https://hdl.handle.net/20.500.12557/5262
Cevallos, C., Ninancuro, M. Evaluación del comportamiento Físico-mecánico de las unidades de ladrillo de concreto para albañilería, elaboradas con árido de residuos de construcción y demolición (R.C.D.) y cemento Pórtland tipo IP, fabricadas en la ciudad de Cusco []. PE: Universidad Andina del Cusco; 2021. https://hdl.handle.net/20.500.12557/5262
@misc{renati/959522, title = "Evaluación del comportamiento Físico-mecánico de las unidades de ladrillo de concreto para albañilería, elaboradas con árido de residuos de construcción y demolición (R.C.D.) y cemento Pórtland tipo IP, fabricadas en la ciudad de Cusco", author = "Ninancuro Calluco, Margareth Shirly", publisher = "Universidad Andina del Cusco", year = "2021" }
Incidencia (100% - presente en todas las muestras) y presencia (55.75% en cantidad promedio
respecto al total de la muestra) del Grupo A, compuesto por concreto, ladrillos, tejas y
materiales cerámicos de acuerdo al protocolo europeo, por lo tanto fue el material que se opta
a utilizar, lo que a su vez genera que las muestras obtenidas del R.C.D. procesado estuviesen
compuestas por concreto, ladrillos, tejas y materiales cerámicos. Seguidamente al ensayar el
material obtenido por granulometría, se determinó que se tiene una proporción agregado grueso
a agregado fino de 4 a 1 aproximadamente (80.13% a 19.80 exactamente) %, del cual se utiliza
netamente el material considerado agregado fino por tratarse de un diseño de mortero.
Finalmente, de los resultados de los ensayos clasificatorios para las unidades de R.C.D. se
obtiene que las unidades elaboradas con árido R.C.D. y cemento portland tipo IP, cumplen con
todo lo indicado por el R.N.E. Norma Técnica E.070 Albañilería, (2006), para Bloque tipo P(1):
Para el ensayo de variación dimensional se obtienen los resultados: +0.30% y -0.30% para el
largo, +0.77% y -0.70% para el ancho, +1.17% y -1.15% para la altura cumpliendo en todas las
dimensiones con la norma técnica que indica una variación dimensional menor al 2.0% respecto
a la dimensión siendo evaluada. Para el ensayo de alabeo se obtienen como resultados: para
convexidad 3.00 mm y para concavidad 1.50mm, por lo que considera que el alabeo máximo
con valor de 3.00 mm, cumpliendo con la norma técnica que indica un alabeo menor que
4.00mm. Para ensayo de resistencia a compresión característica a los 28 días se obtiene el
resultado de 148.01 kg/cm2 para un grupo de 08 muestras, cumpliendo con la norma técnica
que indica al menos 50.00 kg/cm2 (es_PE)
This research was oriented at evaluating the physical-mechanical behavior of masonry concrete
units made from aggregate of construction and demolition waste (CDW) and Portland cement
type IP manufactured in the city of Cusco, contrasting the results with what is required for the
classification of masonry units by the R.N.E. Technical Standard E.070 Masonry, (2006) to
determine the capacities and means in which these can be used.
First, a survey was conducted to the public functionaries e material dispatchers whose functions
were related to the management of the CDW, then CDW samples were classified by the
European protocol and local Peruvian regulations (solid waste law, handling and management)
both before and after being processed. Being that a mortar design was being used, it was decided
to use the CDW aggregate as a replacement for the fine aggregate in the mixture, for which the
CDW aggregate was tested for moisture content, granulometry, Atterberg limits, specific
gravity and absorption percentage from the fine aggregate.
The supplies and materials for the mortar (cement, water and aggregate) of the masonry units
were studied and analyzed prior to the mix design.
After the mix design, 18-hole block-type masonry units were made with approximate
dimensions of 23.3, 13.6 and 8.6cm in length, width and height respectively, poured with the
calculated dosage, a total of 53 units were made because 3 of them were damaged in the
demolding process. Of these, half of the units were destined for destructive tests as follows: 12
units to be tested to compressive strength in units, 4 units for each age of 7, 14 and 28 days, 4
units to be tested to modulus of rupture for an age of 28 days and finally 9 to be tested in piles
of 3 units for the age of 28 days to compressive strength in piles in a complementary way to
this research. The other half was destined for the non-destructive tests of dimensional variation,
warpage, weight, absorption, maximum absorption, suction and percentage of voids.
The results of the surveys indicate that of the public functionaries 90.91% of the total have a
basic level of knowledge regarding the CDW, while the material dispatchers have a level
between null and minimum 73.33% and 26.67% of the total respectively. The results obtained
from the unprocessed RCD material indicate that within the samples there was a higher
incidence (100% - present in all samples) and presence (55.75% in average quantity from the
total sample) from Group A, composed by concrete, bricks, tiles and ceramic materials according to the European protocol, therefore it was the material chosen to be used, which
means that the samples obtained from the processed RCD were made up of concrete, bricks,
tiles and ceramic materials. Subsequently, when testing the material obtained to granulometry,
it was determined that there is a coarse aggregate to fine aggregate ratio of approximately 4 to
1 (80.13% to 19.8% exactly), of which the material considered fine aggregate is the chosen to
be used because it is a mortar design.
Finally, from the results of the qualifying tests for the CDW units, it is obtained that the units
made with CDW aggregate and Portland cement type IP comply with everything indicated by
the R.N.E. Technical Standard E.070 Masonry (2006), for Block type P( 1): For the
dimensional variation test, the results: +0.30% and -0.30% for the length,
+0.77% and -0.70% for the width, +1.17% and -1.15% for the height comply in all the
dimensions with the Technical Standard that indicates a dimensional variation of less than 2.0%
from the dimension being evaluated. For the warpage test, the following results are obtained:
for convexity 3.00 mm and for concavity 1.50 mm, so it is considered that the maximum
warpage is 3.00 mm, complying with the Technical Standard that indicates warping less than
4.00 mm. For the characteristic compressive strength test at 28 days, it is obtained a value of
148.01 kg/cm2 for a group of 08 samples, complying with the Technical Standard that indicates
at least 50.00 kg/cm2 (en_US)
Evaluación del comportamiento Físico-mecánico de las unidades de ladrillo de concreto para albañilería, elaboradas con árido de residuos de construcción y demolición (R.C.D.) y cemento Pórtland tipo IP, fabricadas en la ciudad de Cusco (es_PE)
info:eu-repo/semantics/bachelorThesis (es_PE)
Universidad Andina del Cusco. Facultad de Ingeniería y Arquitectura (es_PE)