Bibliographic citations
This is an automatically generated citacion. Modify it if you see fit
Bustinza, F., (2023). Análisis de riesgo de incendio en establecimiento de salud [Tesis, Universidad Nacional de Ingeniería]. http://hdl.handle.net/20.500.14076/26747
Bustinza, F., Análisis de riesgo de incendio en establecimiento de salud [Tesis]. PE: Universidad Nacional de Ingeniería; 2023. http://hdl.handle.net/20.500.14076/26747
@misc{renati/712755,
title = "Análisis de riesgo de incendio en establecimiento de salud",
author = "Bustinza Orosco, Fernando Jesús",
publisher = "Universidad Nacional de Ingeniería",
year = "2023"
}
Full metadata record
Taipe Rojas, Javier Enrique
Bustinza Orosco, Fernando Jesús
Bustinza Orosco, Fernando Jesús
2023-12-04T21:59:07Z
2023-12-04T21:59:07Z
2023
http://hdl.handle.net/20.500.14076/26747
La presente tesis realiza el análisis de riesgo de incendio en un establecimiento de salud, aplicando la metodología Fire Risk Assessment Method for Engineering - FRAME. Se utilizó el software de Excel que contiene las operaciones de la metodología FRAME, para calcular los diferentes niveles de riesgo, para finalmente calcular el riesgo inicial de incendio “Ro” y el nivel de riesgo de incendio de los diferentes niveles de piso del establecimiento de salud. El establecimiento de salud es una infraestructura compleja; ya que cuenta con diferentes áreas de atención, donde brinda asistencia médica, partos hasta el internamiento de personas. Esto implica que la infraestructura debe contar con el equipamiento adecuado para prevenir y controlar un incendio, con la finalidad de garantizar un sitio seguro para las personas y mantener la continuidad de los servicios de atención médica para los pacientes. El riesgo inicial de incendio, es menor a 1; mientras que el riesgo de patrimonio y/o bienes, para el tercer y cuarto piso, es mayor a 1; el riesgo para las personas, en todos los niveles de piso, es menor a 1; y el riesgo para las actividades, en todos los niveles de piso, es mayor a 1. El nivel de riesgo para el patrimonio y/o bienes, riesgo para las personas, y riesgo para las actividades; es mayor en el cuarto piso. Por ello, se tomará como nivel de referencia con respecto a los otros niveles de pisos, para poder implementar medidas de prevención y control de incendio adecuado y efectivo. Se identifica que en los diferentes niveles de pisos existen áreas críticas que no cuenta con un sistema adecuado para prevenir y controlar un incendio, como es un sistema de rociadores, sistema automático especial, falta de hidrantes, falta de plan de contingencia, entre otros. Como también la poca capacidad de almacenamiento de agua contraincendios que cuenta el establecimiento de salud. Asimismo, el establecimiento de salud cuenta en todos sus niveles de pisos con extintores manuales para las diferentes clases de fuego, sistema automático de detección, con distribución de gabinetes contraincendios. Sus infraestructuras cuentan con resistencia al fuego. (es)
This thesis analyzes the risk of fire in a health establishment, applying the Fire Risk Assessment Method for Engineering - FRAME methodology. Using the Excel software that contains the operations of the FRAME methodology, to calculate the different risk levels, to finally calculate the initial fire risk “Ro“ and the fire risk level of the different floor levels of the health facility. The health establishment is a complex infrastructure, since it has different care areas, where it provides medical assistance, childbirth to the hospitalization of people. That is why the infrastructure must have adequate equipment to prevent and control a fire. In order to guarantee a safe place for people and maintain the continuity of health care services for patients. The initial fire risk is less than 1; while the risk of equity and/or assets, for the third and fourth floors, is greater than 1; the risk to people, at all floor levels, is less than 1; and risk to activities. at all floor levels, it is greater than 1. The level of risk for assets and/or assets, risk for people, and risk for activities; it is higher on the fourth floor. That is why it will be taken as a reference level with respect to the other floor levels, in order to implement adequate and effective fire prevention and control measures. It is identified that in the different floor levels there are critical areas that do not have an adequate system to prevent and control a fire, such as a sprinkler system, special automatic system, lack of hydrants, lack of contingency plan, among others. As well as the low capacity for fire-fighting water storage that the health facility has. Likewise, the health establishment has manual fire extinguishers for the different classes of fire, an automatic detection system, and distribution of fire cabinets at all floor levels. Its infrastructures have fire resistance. (en)
Tesis (es)
application/pdf (es)
spa (es)
Universidad Nacional de Ingeniería (es)
info:eu-repo/semantics/restrictedAccess (es)
http://creativecommons.org/licenses/by-nc-nd/4.0/ (es)
Universidad Nacional de Ingeniería (es)
Repositorio Institucional - UNI (es)
Análisis de riesgo de incendio (es)
Establecimiento de salud (es)
Método FRAME (es)
Análisis de riesgo de incendio en establecimiento de salud (es)
info:eu-repo/semantics/bachelorThesis (es)
Universidad Nacional de Ingeniería. Facultad de Ingeniería Ambiental (es)
Ingeniería de Higiene y Seguridad Industrial (es)
Título Profesional (es)
Ingeniero de Higiene y Seguridad Industrial (es)
PE (es)
http://purl.org/pe-repo/ocde/ford#2.11.02 (es)
Ingeniería (es)
http://purl.org/pe-repo/renati/nivel#tituloProfesional (es)
10343176
https://orcid.org/0000-0002-9488-5836 (es)
46903995
022016
Villena Chávez, Jorge Alberto
Robles García, Eusebio
http://purl.org/pe-repo/renati/type#tesis (es)
Pública
This item is licensed under a Creative Commons License